A reproducible engineering benchmark for a 400 V DC → 230 Vrms, 50 Hz inverter. Model an LC-filtered H-bridge, apply electrical disturbances, and compare cascaded PI, sliding-mode, adaptive sliding-mode and constrained model-predictive control using measured simulation results.
Quick start · Results · Model · Controller derivations · Protocol · فارسی
- Two plant fidelities: a fast averaged inverter and event-resolved unipolar SPWM.
- Four controllers: cascaded PI, boundary-layer SMC, adaptive-gain SMC and a 16-step constrained QP MPC using OSQP.
- Eight scenarios: load step, DC sag, sensor noise, L/C mismatch, actuator delay, dynamic diode-bridge load, combined disturbances and nominal operation.
- Transparent metrics: coherent THD, tracking RMSE, fundamental/RMS voltage, cycle-based recovery, saturation, peak current and solver diagnostics.
- Reproducible experiments: seeded noise, configurations, raw waveforms, dependency versions and a hash of the simulation source.
- Extensible software: installable package, CLI, Streamlit explorer, notebook, independent numerical checks and cross-platform CI.
This is a simulation-based digital-twin foundation. Physical hardware calibration and validation are future work. See the model scope before interpreting the results as evidence about a physical inverter.
Requires Python 3.11 or newer.
git clone https://github.com/mohammmad357/PowerControlLab.git
cd PowerControlLab
python -m venv .venvActivate the environment: .venv\Scripts\activate on Windows, or
source .venv/bin/activate on macOS/Linux. Then:
python -m pip install -e ".[dev,dashboard]"
python main.py --controller smc --load nonlinearThe command prints computed metrics and writes metrics.json, run.json,
waveforms.npz, traces.png and a benchmark CSV under results/.
# Compare four controllers on the load step
powercontrollab --controller all --scenario load-step
# Run the full 32-case averaged benchmark
powercontrollab --controller all --scenario all
# Resolve switching ripple with exact PWM transition times
powercontrollab --controller smc --mode switching
# Change nominal engineering parameters (SI units)
powercontrollab --controller mpc --inductance 0.0025 --capacitance 0.000025
# Explore experiments in a local dashboard
streamlit run dashboard/app.pyUse a fresh --output directory to preserve different experiments; rerunning the
same output path replaces that run's artifacts. --no-plots and --no-raw produce compact
metric-only experiments. Run powercontrollab --help for all options.
These numbers are generated by python scripts/reproduce.py, using fixed gains,
400 V DC, 230 Vrms/50 Hz, 20 kHz control, a 5 µs integration step and seed 7.
The table uses the averaged plant and the final five complete cycles, [140,240) ms.
THD includes orders 2–40. Switching ripple is evaluated separately.
| Scenario | Controller | THD₂–₄₀ [%] | Steady RMSE [V] | Recovery [ms] |
|---|---|---|---|---|
| nominal | Cascaded PI | 0.000 | 0.872 | 20.00 |
| nominal | SMC | 0.000 | 0.047 | 20.00 |
| nominal | Adaptive SMC | 0.000 | 0.047 | 20.00 |
| nominal | MPC | 0.000 | 0.018 | 20.00 |
| nonlinear | Cascaded PI | 3.152 | 7.619 | not settled |
| nonlinear | SMC | 2.470 | 5.909 | not settled |
| nonlinear | Adaptive SMC | 1.627 | 3.872 | 20.00 |
| nonlinear | MPC | 1.058 | 2.510 | 20.00 |
Recovery means one-cycle RMS tracking error stays within 2% of requested RMS voltage through the end of the run. Its origin is the event or the end of startup; the minimum measurable value is one cycle (20 ms). “Not settled” is an explicit outcome. No controller ordering is hard-coded. These tunings and experiments do not establish universal superiority. See the complete protocol.
All 40 averaged/switching results · Averaged CSV · Switching CSV · Numerical convergence
flowchart LR
DC[400 V DC] --> HB[H-bridge]
HB --> L[2 mH + 0.15 ohm]
L --> OUT[Output voltage]
OUT --> LOAD[Resistive or diode-bridge RC load]
OUT --> C[20 uF shunt capacitor]
REF[230 Vrms / 50 Hz reference] --> CTRL[PI / SMC / Adaptive SMC / MPC]
OUT --> SENSE[Sampled voltage and current sensing]
SENSE --> CTRL
CTRL --> DELAY[Duty limit + optional delay]
DELAY --> PWM[Averaged bridge / unipolar SPWM]
PWM --> HB
The states follow
The nonlinear load adds a third state for a diode-bridge DC capacitor. Splitting at switching edges prevents duty quantization on the integration grid. Controllers receive the same observations; mismatch scenarios retain nominal controller parameters.
Read the plant equations and controller laws with gain units for the assumptions behind every result. The topology is consistent with voltage-source LC inverter practice described by Texas Instruments; this project uses independently chosen parameters and controller implementations.
from powercontrollab import PlantConfig, SimulationConfig, simulate
from powercontrollab.analysis import compute_metrics
plant = PlantConfig(inductance=2e-3, capacitance=20e-6)
experiment = SimulationConfig(scenario="dc-sag", seed=7)
result = simulate("mpc", plant=plant, config=experiment)
print(compute_metrics(result))
# result.time, result.voltage, result.current, result.modulation, ...The demo notebook covers a nominal comparison, a disturbed run and
harmonic analysis. Install python -m pip install -e ".[notebook]" to use it locally.
python -m pytest
python -m ruff check .
python -m ruff format --check .
python scripts/reproduce.py
python scripts/validate_numerics.pyTests check energy balance, RK4 against a matrix exponential, exact PWM averages, known-harmonic THD, MPC against an independent optimizer, anti-windup, solver failure, deterministic noise, actuator delay, convergence, CLI exports and the dashboard. CI also builds the Python distribution.
For the Python 3.13 reference numerical dependency versions, install
python -m pip install -r requirements-repro.txt after the project. Each run records a
source hash and library versions in run.json. CPU timings depend on the machine.
src/powercontrollab/
models/ H-bridge, LC state space and loads
controllers/ PI, SMC, adaptive SMC, constrained MPC
modulation/ Unipolar SPWM with exact edge times
analysis/ Coherent FFT, THD and tracking metrics
simulation.py Sampled-data simulation and disturbances
cli.py Single runs and benchmark matrices
dashboard/ Optional Streamlit explorer
notebooks/ Worked engineering demo
scripts/ Reproduction and refinement studies
artifacts/ Computed reference metrics and figures
docs/ Equations, control laws and protocol
tests/ Physics, numerical and integration checks
See CONTRIBUTING.md for extension contracts. Research directions include parameter identification, current-constrained MPC, delay compensation and hardware validation. Report issues with the command, configuration and seed. Released under MIT; cite the version and commit using CITATION.cff.