go-bacnet

Go Go Reference License CI Codecov Release

go-bacnet is a pure-Go BACnet/IP client library: discover devices, read and write properties, subscribe to change-of-value and alarm notifications, transfer files and manage objects on BACnet/IP (Annex J) over IPv4, including routed networks, foreign-device registration and segmentation. It has no dependencies outside the Go standard library.

New to BACnet? Start with PROTOCOL.md.

Status

Client only. The library is tested on every change against five independent open-source BACnet stacks running in containers (bacnet-stack, BACpypes3, BACnet4J, Worldiety, System.IO.BACnet; INTEROP.md) and its requests are checked against Wireshark's dissector. It has not been validated against physical controllers yet; the checklist for that is docs/FIELD_VALIDATION.md. The API is v0 and can still change between minor versions; RELEASE.md lists every change.

Scope

Transport and network BACnet/IP over IPv4/UDP, BVLC, routed addressing (DNET/DADR), Forwarded-NPDU, foreign-device registration with one BBMD, BDT/FDT management, segmented requests and responses
Discovery Who-Is / I-Am, Who-Has / I-Have, Who-Is-Router-To-Network
Object access ReadProperty, ReadPropertyMultiple, WriteProperty, WritePropertyMultiple, ReadRange, Add/RemoveListElement, CreateObject, DeleteObject, AtomicRead/WriteFile
Notifications SubscribeCOV, SubscribeCOVProperty, SubscribeCOVPropertyMultiple, COV and EventNotification reception, AcknowledgeAlarm, GetEventInformation, GetAlarmSummary, GetEnrollmentSummary
Other services time synchronization, text message, private transfer, WriteGroup, LifeSafetyOperation, and (opt-in) DeviceCommunicationControl and ReinitializeDevice

The complete matrix, with how well each capability is validated, is docs/CLIENT_SUPPORT.md.

Not in scope: a BACnet server or device object model, BBMD server, MS/TP, BACnet/IPv6, BACnet/SC, BTL certification. BACnet/IP has no authentication or encryption and this library adds none (SECURITY.md).

A command-line client built on this library lives in otfabric/bacnetctl.

Install

go get github.com/otfabric/go-bacnet@latest

Requires Go 1.23 or newer.

Getting started

package main

import (
	"context"
	"fmt"
	"log"
	"time"

	"github.com/otfabric/go-bacnet"
	"github.com/otfabric/go-bacnet/client"
)

func main() {
	c, err := client.New() // binds UDP port 47808
	if err != nil {
		log.Fatal(err)
	}
	defer c.Close()

	ctx := context.Background()
	devices, err := c.Discover(ctx, client.DiscoveryOptions{Window: 3 * time.Second})
	if err != nil {
		log.Fatal(err)
	}
	name := bacnet.PropertyReference{Identifier: bacnet.PropertyObjectName}
	for _, d := range devices {
		val, err := c.ReadProperty(ctx, d.Target(), d.DeviceID(), name)
		if err != nil {
			fmt.Printf("device %d at %s: %v\n", d.Instance, d.Address, err)
			continue
		}
		fmt.Printf("device %d at %s: %s\n", d.Instance, d.Address, val.Character.Value)
	}
}

A device whose address you already know needs no discovery:

c, err := client.New(client.WithLocalAddr("0.0.0.0:0")) // any free local port
// ...
target := client.Target{Endpoint: bip.NewEndpoint(netip.MustParseAddrPort("192.168.1.20:47808"))}
av1 := bacnet.ObjectIdentifier{Type: bacnet.ObjectTypeAnalogValue, Instance: 1}
pv, err := c.ReadProperty(ctx, target, av1, bacnet.PropertyReference{Identifier: bacnet.PropertyPresentValue})

These and further examples (writing with a priority, COV subscriptions, logging) are compiled as part of the test suite: see client/example_test.go and examples/.

Things to know before you use it

  • One client, one socket. A Client owns one UDP socket and is safe for concurrent use; requests are multiplexed on it by invoke ID. Create one per local interface and keep it; Close releases the socket and fails pending requests with bacnet.ErrClosed.
  • Port 47808. Devices answer Who-Is with a broadcast to port 47808, so discovery needs the client bound there (the default), and only one process on a host can be. Unicast requests work from any port (WithLocalAddr("0.0.0.0:0")).
  • Broadcasts stop at routers. A Who-Is goes to the broadcast address of every local subnet. To discover devices on another IP subnet, register as a foreign device with a BBMD there (WithForeignDevice) or send a unicast Who-Is (SendWhoIs). WithInterface restricts broadcasts to one interface.
  • Timeouts. A request without an answer fails with bacnet.ErrTimeout after the APDU timeout (3 s) times the attempts (reads are retransmitted 3 times; writes never). A context deadline or cancellation ends it earlier and is preserved for errors.Is. See WithTransactionOptions.
  • Writes can be ambiguous. A write is sent once. If no answer arrives the device may or may not have applied it: the call returns *bacnet.OutcomeUnknownError, never a plain timeout. Read the value back before repeating a write that is not idempotent.
  • Errors are typed. A device's Error, Reject and Abort PDUs come back as *bacnet.ErrorResponse, *bacnet.RejectError and *bacnet.AbortError with standard names; ReadPropertyMultiple reports per-property errors inside its results. ERRORS.md has the whole taxonomy.
  • Dangerous services are opt-in. DeviceCommunicationControl, ReinitializeDevice and Write-BDT fail locally unless enabled with WithDeviceManagementEnabled / WithNetworkManagementEnabled.
  • Silent by default. No logging unless you pass WithLogger (OBSERVABILITY.md).
  • Character strings. CharacterString.Value holds the octets as received. Use Text() to get a Go string from devices that send UCS-2 or ISO 8859-1.

Documentation

Document Contents
PROTOCOL.md BACnet primer
API.md Client behavioural contract: lifecycle, ownership, timeouts, result models
ERRORS.md Sentinels, remote PDUs, outcome-unknown
OBSERVABILITY.md Logging and diagnostics
ARCHITECTURE.md Packages, dependency rules, client runtime
docs/CLIENT_SUPPORT.md Every capability and its evidence level
INTEROP.md Scenario-by-peer results and how to run them
docs/COMPATIBILITY.md Peer quirks and hardware results
docs/CLIENT_PROFILE.md Descriptive standards profile
docs/STANDARD_BASELINE.md Normative baseline
docs/FIELD_VALIDATION.md Physical-device checklist
PLAN.md Forward plan
RELEASE.md Release history
CONTRIBUTING.md Local checks and interop how-to
TESTING.md Test tiers, prerequisites, coverage and fuzz procedure
LIMITATIONS.md What is not implemented or not verified
SECURITY.md Trust model and reporting

License

MIT — see LICENSE.